Equipment summary
Specifications and scope
| Unit ID | JJ-FORTUNE-230-167 |
|---|---|
| Manufacturer | Fortune Electric |
| Manufacturer basis | Nameplate drawing reviewed |
| Rating | 100/133/167 MVA; 35 MVA tertiary |
| Voltage / output | 230/34.5 kV with 13.3 kV buried-delta tertiary |
| Frequency | 60 Hz |
| Vector group | YNyn0d1 |
| Tertiary | 13.3 kV; confirm winding duty and MVA rating |
| Quantity | 1 unit |
| Availability | Available; subject to prior sale and written confirmation |
| Condition basis | Brand new, never used and never energized |
| Condition confirmed by J&J | |
| Current location | USA |
| Listing information reviewed |
Technical values and record basis
Supplied design nameplate and outline drawings; blank final values remain unconfirmed.
| Phases | Three-phase |
|---|---|
| Cooling | ONAN / ONAF1 / ONAF2 |
| Temperature rise | 65°C winding and oil, design basis |
| Conductor / fluid | Copper / Type II mineral oil |
| Tap changer | HV OLTC; 207–253 kV (±10%), design basis |
| Insulation / BIL | HV line 750 kV; HV neutral and LV 200 kV; tertiary 110 kV |
| Tertiary duty | 13.3 kV buried delta, 35 MVA |
| Approximate total weight | 425,000 lb, drawing basis |
| Approximate shipping weight without oil | 297,400 lb, drawing basis |
| Application | Suitable for step-up duty as shown on the drawing |
Details to confirm for this listing
- Final tested impedance and base, manufacture year and final tap-switch specification
- Final oil quantity, dimensions, tests, current preservation and complete accessories
Technical highlights
- Three-phase, 60 Hz; ONAN/ONAF1/ONAF2 cooling; 65 C winding rise
- Grounded-wye / grounded-wye / delta; vector group YNyn0d1
- HV OLTC range 207-253 kV; 13.3 kV, 35 MVA buried-delta tertiary
- Copper windings, Type II mineral oil
- Nameplate drawing identifies suitability for step-up operation; final test results and impedance available subject to confirmation
Evidence reviewed
Nameplate drawing reviewed
Records apply only to the stated unit or design basis.
Availability and terms
Available; subject to prior sale and written confirmation
Ask for the current technical package, price, included accessories and delivery terms.
Confirm the purchase and delivery scope
Ask J&J to confirm the proposed unit’s allocation, price, inspection access, included accessories, loading and freight boundary, receiving arrangements, release schedule, deposit or reservation terms and any applicable warranty. Photos, matching records and inspection arrangements are coordinated through J&J.
Request written termsCheck this transformer against your project
Compare the complete winding arrangement and condition evidence before requesting a quote. A matching voltage ratio alone does not establish suitability.
- Compare 230/34.5 kV transformers
- Match MVA, voltage, impedance, taps and winding connections
- Review seven transformer condition risks before purchase
For this listing’s photographs, reports, pricing and current status, call 346-276-9540 or email Tommy with unit ID JJ-FORTUNE-230-167.