Company base: Sugar Land, Texas · Nationwide sales · Tommy Marco

346-276-9540 tommy@jjtransformers.com

Transformer opportunity · JJ-WEG-66-90

WEG 54/79/90 MVA 66/34.5 kV Transformer

Equipment location: USA. J&J is based in Sugar Land, Texas and serves projects nationwide.

Condition: Brand new, never used and never energized. WEG 54/79/90 MVA transformer with a 66 kV delta high side and 34.5 kV grounded-wye low side. Drawings and specifications are available from J&J on request. Availability is subject to prior sale and written confirmation. Contact Tommy Marco at 346-276-9540 or tommy@jjtransformers.com with MVA, voltages, quantity, site, and need-by date. Listing information reviewed .

Availability & record date
Availability confirmedConfirmed by J&J Request current allocation and release terms · subject to prior sale

Equipment summary

Specifications and scope

Unit IDJJ-WEG-66-90
ManufacturerWEG
Manufacturer basisApproval nameplate and preliminary outline drawings reviewed
Rating54/79/90 MVA
Voltage / output66 kV delta / 34.5 kV grounded wye
Frequency60 Hz
Vector groupDyn1
TertiaryNot documented; confirm the complete winding arrangement
Quantity1 unit
AvailabilityAvailable; subject to prior sale and written confirmation
Condition basisBrand new, never used and never energized
Condition confirmed by J&J
Current locationUSA
Listing information reviewed

Technical values and record basis

Approval nameplate and preliminary design drawings; final tested unit values require confirmation.

PhasesThree-phase
CoolingONAN / ONAF1 / ONAF2
Temperature rise60°C continuous design basis; confirm the project ambient duty
Conductor / fluidCopper / inhibited Type II mineral oil
Tap changerLV OLTC; 31.05–37.95 kV (±10%); 16 raise / 16 lower steps of 0.625%
Impedance and baseNominal design H–X: 8.63% at 54 MVA, 66/34.5 kV, 85°C
Insulation / BILHV 350 kV; LV line 200 kV; LV neutral 150 kV
Total design weight210,903 lb
Shipping weight without oil131,520 lb, drawing basis
Oil volume7,274 US gal, drawing basis

Details to confirm for this listing

  • Final nameplate, tested impedance, accepted temperature-rise and ambient basis
  • Final installation drawings, accessories, dimensions, current preservation and shipping configuration

Technical highlights

  • Three-phase, 60 Hz; ONAN/ONAF1/ONAF2 cooling
  • Vector group Dyn1; 66 kV delta / 34.5 kV grounded wye
  • Low-side LTC with 16 raise and 16 lower steps of 0.625%
  • WEG approval drawings are not final installation drawings
  • Final impedance, temperature-rise basis, condition, and shipping scope to confirm in the technical package

Evidence reviewed

Approval nameplate and preliminary outline drawings reviewed

Records apply only to the stated unit or design basis.

Availability and terms

Available; subject to prior sale and written confirmation

Ask for the current technical package, price, included accessories and delivery terms.

Confirm the purchase and delivery scope

Ask J&J to confirm the proposed unit’s allocation, price, inspection access, included accessories, loading and freight boundary, receiving arrangements, release schedule, deposit or reservation terms and any applicable warranty. Photos, matching records and inspection arrangements are coordinated through J&J.

Request written terms

Check this transformer against your project

Compare the complete winding arrangement and condition evidence before requesting a quote. A matching voltage ratio alone does not establish suitability.

For this listing’s photographs, reports, pricing and current status, call 346-276-9540 or email Tommy with unit ID JJ-WEG-66-90.

Compare related equipment

Browse transformer types and voltages

Need a different unit?

Send the exact requirement.

Include MVA or MW, voltage, quantity, site, and need-by date for a private match.

Email for Availability