| Compare | 105 MVA 161/34.5 kV Siemens Energy TransformerJJ-SIEMENS-161-105 | 220 MVA 345/34.5 kV Prolec GE TransformerJJ-TX-002 |
|---|---|---|
| Manufacturer | Siemens Energy | Prolec GE |
| Rating / output | 63/84/105 MVA | 132/176/220 MVA; 46.2/61.6/77 MVA tertiary |
| Voltage / winding arrangement | 161/34.5 kV with 13.8 kV tertiary | 345/34.5 kV with 13.8 kV delta tertiary |
| Vector group | Not stated in supplied records | Grounded Wye–Wye / Delta; clock to confirm |
| Frequency | 60 Hz | 60 Hz |
| Cooling | ONAN / ONAF1 / ONAF2 | ONAN / ONAF / ONAF |
| Impedance and base | H–X: 9.25% at 63 MVA; 12.34% at 84 MVA; 15.42% at 105 MVA | Design H–X: 12.0% at 132 MVA |
| Tap changer | HV OLTC; 144.9–177.1 kV (±10%); ±8 steps of 1.25% | Not documented; confirm with J&J |
| Insulation / BIL | HV line 650 kV; HV neutral and LV 200 kV; tertiary 110 kV | Not documented; confirm with J&J |
| Quantity represented | 1 nameplate-documented unit | 1 documented unit |
| Technical details / open items | 2022 manufacture shown on nameplate; three-phase, 60 Hz, copper windings; ONAN/ONAF1/ONAF2 cooling and approximately 144.9-177.1 kV HV OLTC range; Nameplate identifies 34.5 kV low-side and 13.8 kV additional winding; Supplied equipment photo shown; request the connection diagram, complete matching records and preservation history through J&J | Collector step-up duty; ONAN/ONAF/ONAF, 60 Hz, three-phase; Grounded-wye / grounded-wye / delta winding configuration; Nominal design H-X impedance: 12.0% on a 132 MVA base |
| Evidence reviewed | Serial-specific nameplate photograph reviewed | Serial-specific nameplate and approval drawings reviewed |
| Technical value basis | Supplied individual nameplate photograph; verify the winding diagram and current preservation. | Supplied nameplate and approval drawings; design values require matching final factory records. |
| Details to confirm | Complete winding connection/clock diagram and tertiary MVA duty; Current preservation, matching tests, dimensions and accessory completeness | Final tested impedance, insulation levels, complete tap schedule and approved drawing revision; Overall and shipping dimensions, shipping weight, accessory schedule and current preservation |
| Represented condition | Brand new, never used and never energized; 2022 nameplate reviewed | Brand new, never used and never energized; approval drawings reviewed |
| Equipment location | USA | USA |
| Technical records reviewed | 2026-10-08 | 2026-10-08 |
| Availability | Available; nameplate reviewed; subject to prior sale and written reconfirmation | Available; nameplate and approval drawings reviewed; subject to prior sale and written confirmation |
| Availability last confirmed | 2026-09-24 | 2026-09-24 |
| Shipping estimate | Request a written dispatch and delivery schedule | Request a written dispatch and delivery schedule |
| Nameplate reviewed | Yes — request the unit package | Yes — request the unit package |
| Drawings reviewed | Not recorded as reviewed; request them | Yes — request matching unit drawings |
| Factory test report reviewed | Not recorded as reviewed; request test records | Not recorded as reviewed; request test records |
| This unit only | Request more info | Request more info |
One request
Request Availability for Your Shortlist.
Email Tommy to discuss these options. The listing IDs will already be in the email subject.
What still needs to be checked?
Confirm frequency, cooling-stage ratings, impedance and its base, taps, vector group, grounding, BIL, site conditions and included scope against the project specification. A table cannot approve the fit.