| Compare | 71.2 MVA Prolec GE 240/120-13.8 kV GSUJJ-PGE-240-71 | 220 MVA 345/34.5 kV Prolec GE TransformerJJ-TX-002 |
|---|---|---|
| Manufacturer | Prolec GE | Prolec GE |
| Rating / output | 42.7/57/71.2 MVA at 60 Hz | 132/176/220 MVA; 46.2/61.6/77 MVA tertiary |
| Voltage / winding arrangement | 240/120 kV grounded-wye dual-voltage to 13.8 kV delta | 345/34.5 kV with 13.8 kV delta tertiary |
| Vector group | Grounded Wye–Delta; clock to confirm | Grounded Wye–Wye / Delta; clock to confirm |
| Frequency | 60 Hz | 60 Hz |
| Cooling | ONAN / ONAF / ONAF | ONAN / ONAF / ONAF |
| Impedance and base | Not documented; confirm with J&J | Design H–X: 12.0% at 132 MVA |
| Tap changer | Dual-voltage HV DETC; confirm series/parallel reconnection and the complete 11-position tap table | Not documented; confirm with J&J |
| Insulation / BIL | HV winding: 900 kV series / 650 kV parallel; HV bushings 900 kV; LV 110 kV; HV neutral 250 kV | Not documented; confirm with J&J |
| Quantity represented | 1 documented unit | 1 documented unit |
| Technical details / open items | Generator step-up transformer; three-phase, 60 Hz, ONAN/ONAF/ONAF; Dual-voltage grounded-wye high side rated 240 or 120 kV with 13.8 kV delta low side; De-energized tap changer, copper windings, mineral oil, and suitable-for-step-up designation; Manufacture date is not completed on the reviewed drawing; 2012 is the drawing-approval date, not a claimed build year | Collector step-up duty; ONAN/ONAF/ONAF, 60 Hz, three-phase; Grounded-wye / grounded-wye / delta winding configuration; Nominal design H-X impedance: 12.0% on a 132 MVA base |
| Evidence reviewed | Serial-specific approval nameplate drawing reviewed | Serial-specific nameplate and approval drawings reviewed |
| Technical value basis | Supplied approval nameplate drawing; its approval date is not a manufacture date. | Supplied nameplate and approval drawings; design values require matching final factory records. |
| Details to confirm | Final manufacture year, tested impedance/base and selected voltage/tap connection; Current preservation, final oil quantity, dimensions, shipping weight and accessory scope | Final tested impedance, insulation levels, complete tap schedule and approved drawing revision; Overall and shipping dimensions, shipping weight, accessory schedule and current preservation |
| Represented condition | Brand new, never used and never energized | Brand new, never used and never energized; approval drawings reviewed |
| Equipment location | USA | USA |
| Technical records reviewed | 2026-10-08 | 2026-10-08 |
| Availability | Available; approval nameplate drawing reviewed; subject to prior sale and written reconfirmation | Available; nameplate and approval drawings reviewed; subject to prior sale and written confirmation |
| Availability last confirmed | 2026-09-24 | 2026-09-24 |
| Shipping estimate | Request a written dispatch and delivery schedule | Request a written dispatch and delivery schedule |
| Nameplate reviewed | Yes — request the unit package | Yes — request the unit package |
| Drawings reviewed | Yes — request matching unit drawings | Yes — request matching unit drawings |
| Factory test report reviewed | Not recorded as reviewed; request test records | Not recorded as reviewed; request test records |
| This unit only | Request more info | Request more info |
One request
Request Availability for Your Shortlist.
Email Tommy to discuss these options. The listing IDs will already be in the email subject.
What still needs to be checked?
Confirm frequency, cooling-stage ratings, impedance and its base, taps, vector group, grounding, BIL, site conditions and included scope against the project specification. A table cannot approve the fit.
Match the nameplate to the specification · Review surplus equipment records · Procurement checklist