Your equipment shortlist
Compare equipment before you request it.
Review the published facts side by side. Matching a voltage or MVA rating does not establish compatibility. Ask your project engineer to review the complete unit records.
| Compare | New 220 MVA 230/34.5 kV ABB/Hitachi TransformerJJ-230-220-1 | 88 MVA 230/34.5 kV WEG Power TransformerJJ-WEG-230-88 |
|---|---|---|
| Manufacturer | ABB / Hitachi | WEG |
| Rating / output | 132/176/220 MVA | 53/70.5/88 MVA; 18.55/24.675/30.8 MVA tertiary |
| Voltage / winding arrangement | 230/34.5 kV with 13.8 kV buried-delta tertiary | 230/34.5 kV with 13.8 kV stabilizing delta tertiary |
| Vector group | YNyn0d1 — Wye–Wye / Delta | YNyn0d1 |
| Frequency | 60 Hz | 60 Hz |
| Cooling | ONAN / ONAF / ODAF | ONAN / ONAF1 / ONAF2 |
| Impedance and base | H–X: 10.47% at 132 MVA, 230/34.5 kV | Not documented; confirm with J&J |
| Tap changer | HV OLTC; nameplate tap table spans 205.8–254.2 kV; confirm the selected tap and final switch schedule | HV OLTC; 207–253 kV (±10%); 16 raise / 16 lower steps of 0.625% |
| Insulation / BIL | HV line 900 kV; HV neutral, LV and tertiary 200 kV | Not documented; confirm with J&J |
| Quantity represented | 1 unit | 1 nameplate-documented unit |
| Technical details / open items | 132/176/220 MVA, 230 kV grounded-wye high side and 34.5 kV grounded-wye low side; YNyn0d1 connection documented in the manufacturer factory test report; 13.8 kV buried-delta tertiary; 2021 ABB rating-plate drawing; three-phase, 60 Hz, ONAN/ONAF/ODAF cooling; Contact Tommy Marco directly for the technical package, price, and delivery arrangements; Nameplate impedance: 10.47% on a 132 MVA, 230/34.5 kV base; final configuration confirmed with the technical package | Three-phase, 60 Hz, ONAN/ONAF1/ONAF2, vector group YNyn0d1; 230 kV grounded-wye primary, 34.5 kV grounded-wye secondary, and 13.8 kV stabilizing delta tertiary; HV LTC represented at plus/minus 10% with 16 raise and 16 lower steps; 2020 manufacture shown on the reviewed nameplate drawing |
| Evidence reviewed | Manufacturer nameplate and factory test report reviewed | Serial-specific nameplate drawing reviewed |
| Technical value basis | Supplied unit nameplate and historical factory photograph; current inspection and matching factory records remain necessary. | Supplied approval nameplate drawing; the impedance field is not completed. |
| Details to confirm | Current preservation, complete factory-test reports and included accessory schedule; Overall/shipping dimensions, shipping weight, oil quantity and loading arrangements | Final tested impedance/base, all winding/bushing BIL levels and oil quantity; Matching factory tests, current preservation, final dimensions and complete accessories |
| Represented condition | Brand new, never used and never energized | Brand new, never used and never energized; 2020 nameplate reviewed |
| Equipment location | USA | USA |
| Technical records reviewed | 2026-10-08 | 2026-10-08 |
| Availability | Available; confirmed by J&J on September 24, 2026; subject to prior sale and written confirmation | Available; nameplate drawing reviewed; subject to prior sale and written reconfirmation |
| Availability last confirmed | 2026-09-24 | 2026-09-24 |
| Shipping estimate | Request a written dispatch and delivery schedule | Request a written dispatch and delivery schedule |
| Nameplate reviewed | Yes — request the unit package | Yes — request the unit package |
| Drawings reviewed | Yes — request matching unit drawings | Yes — request matching unit drawings |
| Factory test report reviewed | Report reviewed; confirm matching records for each unit | Not recorded as reviewed; request test records |
| This unit only | Request more info | Request more info |
One request
Request Availability for Your Shortlist.
Email Tommy to discuss these options. The listing IDs will already be in the email subject.
What still needs to be checked?
Confirm frequency, cooling-stage ratings, impedance and its base, taps, vector group, grounding, BIL, site conditions and included scope against the project specification. A table cannot approve the fit.
Match the nameplate to the specification · Review surplus equipment records · Procurement checklist