Your equipment shortlist
Compare equipment before you request it.
Review the published facts side by side. Matching a voltage or MVA rating does not establish compatibility. Ask your project engineer to review the complete unit records.
| Compare | 208 MVA 138/34.5 kV Stored Surplus TransformerJJ-TX-201 | Five 110 MVA 138/34.5 kV Kolektor ETRA GSUsJJ-138-110-5 |
|---|---|---|
| Manufacturer | Manufacturer disclosed in the qualified technical package | Kolektor ETRA |
| Rating / output | 125/166/208 MVA | 66/88/110 MVA; 22/29.333/36.666 MVA tertiary |
| Voltage / winding arrangement | 138 kV HV / 34.5 kV LV | 138/34.5 kV with 13.8 kV tertiary |
| Vector group | Grounded wye / grounded wye | YNyn0+d11 |
| Frequency | 60 Hz | 60 Hz |
| Cooling | ONAN / ONAF1 / ONAF2 | ONAN / ONAF1 / ONAF2 |
| Impedance and base | H–X 9% at 125 MVA (supplied design sheet) | Reviewed nameplate H–X: 8.09% at 66 MVA; supplied FAT reports 13.41% at 110 MVA. Match the test and plate to the selected unit. |
| Tap changer | HV OLTC ±8 × 1.25% (±10%); no taps shown on X or Y windings | HV OLTC; 124.2–151.8 kV (±10%); 16 raise / 16 lower steps of 0.625% on the reviewed plate |
| Insulation / BIL | HV line 650 kV; HV neutral, LV line and LV neutral 200 kV | Not documented; confirm with J&J |
| Quantity represented | 1 offered position | 5 units; matching unit packages available on request |
| Technical details / open items | Supplied design data sheet; final unit-specific nameplate and FAT pending.; Ask J&J for the included U.S.-port shipping, commissioning and manufacturer warranty scope in the written offer.; Technical suitability subject to buyer review; Any warranty provider, scope, transfer eligibility, start date and commissioning boundary must appear in the written quotation.; Design basis: ONAN/ONAF1/ONAF2, 60 Hz, 65 C temperature rise; grounded-wye high and low sides.; HV OLTC design range ±10%; preliminary 13.8 kV open-delta tertiary. Final unit-specific configuration requires approval.; Design H-X impedance: 9% at a 125 MVA base. This is a design-sheet value, not a final tested result. | GSU duty; ONAN/ONAF1/ONAF2, 60 Hz, three-phase, vector group YNyn0+d11; Measured impedance: 13.41% on a 110 MVA base at nominal tap; 2020 factory tests passed; those records do not establish current condition; Five-unit lot includes two 2020 builds and three 2021 builds; request all five serial-specific packages before quotation |
| Evidence reviewed | Supplied design data sheet; final unit-specific nameplate and FAT pending | Five-unit opportunity confirmed by seller; rating plate and FAT package reviewed for one unit |
| Technical value basis | Supplied guaranteed design sheet; these are design values, not final tested values for an individually matched unit. | One supplied nameplate and one factory-test package; values are not established for all five units. |
| Details to confirm | Final unit-specific nameplate, approved revision, tested impedance/losses and final tertiary arrangement; Conductor, OLTC switch specification, complete accessories, current photos and preservation or manufacturing progress | All five matching nameplates, insulation levels, approved drawings and factory tests; Reconcile unit-specific impedance bases; confirm current preservation and individual shipping weights |
| Represented condition | Surplus in storage; service history requires confirmation | Brand new, never used and never energized; 2020 factory records reviewed for one unit |
| Equipment location | Dispatch location confirmed with quotation | International; dispatch location confirmed with quotation |
| Technical records reviewed | 2026-10-08 | 2026-10-08 |
| Availability | Stored surplus offered for allocation; current release terms require written confirmation | Available; 5 units represented; remaining unit packages require review; subject to prior sale and written confirmation |
| Availability last confirmed | Request current confirmation | 2026-09-24 |
| Shipping estimate | Release, loading and shipping dates confirmed with quotation | Request a written dispatch and delivery schedule |
| Nameplate reviewed | Not recorded as reviewed; request it | Yes — request the unit package |
| Drawings reviewed | Not recorded as reviewed; request them | Not recorded as reviewed; request them |
| Factory test report reviewed | Not recorded as reviewed; request test records | Report reviewed; confirm matching records for each unit |
| This unit only | Email for specs & price | Email for specs & price |
One request
Request Availability for Your Shortlist.
Email Tommy to discuss these options. The listing IDs will already be in the email subject.
What still needs to be checked?
Confirm frequency, cooling-stage ratings, impedance and its base, taps, vector group, grounding, BIL, site conditions and included scope against the project specification. A table cannot approve the fit.
Match the nameplate to the specification · Review surplus equipment records · Procurement checklist