| Compare | 50 MVA-Class 138/13.8 kV Substation PackageJJ-TX-007 | 120 MVA 138/34.5 kV Georgia Solar GSUJJ-TX-004 |
|---|---|---|
| Manufacturer | Manufacturer to confirm | Georgia Transformer |
| Rating / output | 30/39.9/50 MVA at 55 C; 33.6/44.7/56 MVA at 65 C | 72/96/120 MVA; 25.2/33.6/42 MVA tertiary |
| Voltage / winding arrangement | 138 kV delta / 13.8 kV grounded wye | 138/34.5 kV with 12 kV buried-delta tertiary |
| Vector group | Delta–Grounded Wye; clock to confirm | YNyn0+d1 |
| Frequency | 60 Hz | 60 Hz |
| Cooling | ONAN / ONAF / ONAF | ONAN / ONAF1 / ONAF2 |
| Impedance and base | Not documented; confirm with J&J | Measured H–X: 6.93% at 72 MVA; design value 7.2% |
| Tap changer | Five-position HV DETC: 131.1, 134.55, 138, 141.45 and 144.9 kV (±5%, 2.5% steps) | HV OLTC; 117.3–158.7 kV (±15%); confirm the final switch and step schedule |
| Insulation / BIL | HV 650 kV; LV 110 kV, drawing basis | HV line 650 kV; HV neutral, LV line and LV neutral 200 kV |
| Quantity represented | 1 represented design package | 1 documented unit |
| Technical details / open items | Oil-immersed substation transformer; ONAN/ONAF/ONAF, 60 Hz, three-phase; HV de-energized tap range: 131.1-144.9 kV; Final impedance, serial number, test data, and manufacture date are not populated | Solar GSU design; ONAN/ONAF1/ONAF2, 60 Hz, three-phase; Vector group YNyn0+d1 with HV OLTC and conservator oil system; Nameplate rating is used; an outline-drawing discrepancy requires final seller confirmation |
| Evidence reviewed | Project-specific supplied approval drawings reviewed; final equipment OEM and serial identity require confirmation | Serial-specific nameplate and approval drawings reviewed |
| Technical value basis | Supplied approval design drawings; a completed individual nameplate and final equipment identity have not been established. | Supplied unit nameplate; the nameplate takes precedence over the differing outline-drawing rating. |
| Details to confirm | Final OEM, individual equipment identity, manufacture year, tested impedance and factory reports; Final drawings, current preservation, complete accessories and shipping configuration | Resolve the outline-drawing rating discrepancy and confirm the final drawing revision; Current preservation, complete tests, dimensions and included accessory schedule |
| Represented condition | Brand new, never used and never energized; 2024 approval drawings reviewed; serial identity requires confirmation | Brand new, never used and never energized; approval drawings reviewed |
| Equipment location | USA | USA |
| Technical records reviewed | 2026-10-08 | 2026-10-08 |
| Availability | Available; approval drawings reviewed; unit identity requires documentation; subject to prior sale and written confirmation | Available; engineering package reviewed; subject to prior sale and written reconfirmation |
| Availability last confirmed | 2026-09-24 | 2026-09-24 |
| Shipping estimate | Request a written dispatch and delivery schedule | Request a written dispatch and delivery schedule |
| Nameplate reviewed | Not recorded as reviewed; request it | Yes — request the unit package |
| Drawings reviewed | Yes — request matching unit drawings | Yes — request matching unit drawings |
| Factory test report reviewed | Not recorded as reviewed; request test records | Not recorded as reviewed; request test records |
| This unit only | Email for specs & price | Email for specs & price |
One request
Request Availability for Your Shortlist.
Email Tommy to discuss these options. The listing IDs will already be in the email subject.
What still needs to be checked?
Confirm frequency, cooling-stage ratings, impedance and its base, taps, vector group, grounding, BIL, site conditions and included scope against the project specification. A table cannot approve the fit.
Match the nameplate to the specification · Review surplus equipment records · Procurement checklist