Review the published facts side by side. Matching a voltage or MVA rating does not establish compatibility. Ask your project engineer to review the complete unit records.
| Compare | 50 MVA-Class 138/13.8 kV Substation PackageJJ-TX-007 | Five 110 MVA 138/34.5 kV Kolektor ETRA GSUsJJ-138-110-5 |
|---|---|---|
| Manufacturer | Manufacturer to confirm | Kolektor ETRA |
| Rating / output | 30/39.9/50 MVA at 55 C; 33.6/44.7/56 MVA at 65 C | 66/88/110 MVA; 22/29.333/36.666 MVA tertiary |
| Voltage / winding arrangement | 138 kV delta / 13.8 kV grounded wye | 138/34.5 kV with 13.8 kV tertiary |
| Vector group | Delta–Grounded Wye; clock to confirm | YNyn0+d11 |
| Frequency | 60 Hz | 60 Hz |
| Cooling | ONAN / ONAF / ONAF | ONAN / ONAF1 / ONAF2 |
| Impedance and base | Not documented; confirm with J&J | Reviewed nameplate H–X: 8.09% at 66 MVA; supplied FAT reports 13.41% at 110 MVA. Match the test and plate to the selected unit. |
| Tap changer | Five-position HV DETC: 131.1, 134.55, 138, 141.45 and 144.9 kV (±5%, 2.5% steps) | HV OLTC; 124.2–151.8 kV (±10%); 16 raise / 16 lower steps of 0.625% on the reviewed plate |
| Insulation / BIL | HV 650 kV; LV 110 kV, drawing basis | Not documented; confirm with J&J |
| Quantity represented | 1 represented design package | 5 units; matching unit packages available on request |
| Technical details / open items | Oil-immersed substation transformer; ONAN/ONAF/ONAF, 60 Hz, three-phase; HV de-energized tap range: 131.1-144.9 kV; Final impedance, serial number, test data, and manufacture date are not populated | GSU duty; ONAN/ONAF1/ONAF2, 60 Hz, three-phase, vector group YNyn0+d11; Measured impedance: 13.41% on a 110 MVA base at nominal tap; 2020 factory tests passed; those records do not establish current condition; Five-unit lot includes two 2020 builds and three 2021 builds; request all five serial-specific packages before quotation |
| Evidence reviewed | Project-specific supplied approval drawings reviewed; final equipment OEM and serial identity require confirmation | Five-unit opportunity confirmed by seller; rating plate and FAT package reviewed for one unit |
| Technical value basis | Supplied approval design drawings; a completed individual nameplate and final equipment identity have not been established. | One supplied nameplate and one factory-test package; values are not established for all five units. |
| Details to confirm | Final OEM, individual equipment identity, manufacture year, tested impedance and factory reports; Final drawings, current preservation, complete accessories and shipping configuration | All five matching nameplates, insulation levels, approved drawings and factory tests; Reconcile unit-specific impedance bases; confirm current preservation and individual shipping weights |
| Represented condition | Brand new, never used and never energized; 2024 approval drawings reviewed; serial identity requires confirmation | Brand new, never used and never energized; 2020 factory records reviewed for one unit |
| Equipment location | USA | International; dispatch location confirmed with quotation |
| Technical records reviewed | 2026-10-08 | 2026-10-08 |
| Availability | Available; approval drawings reviewed; unit identity requires documentation; subject to prior sale and written confirmation | Available; 5 units represented; remaining unit packages require review; subject to prior sale and written confirmation |
| Availability last confirmed | 2026-09-24 | 2026-09-24 |
| Shipping estimate | Request a written dispatch and delivery schedule | Request a written dispatch and delivery schedule |
| Nameplate reviewed | Not recorded as reviewed; request it | Yes — request the unit package |
| Drawings reviewed | Yes — request matching unit drawings | Not recorded as reviewed; request them |
| Factory test report reviewed | Not recorded as reviewed; request test records | Report reviewed; confirm matching records for each unit |
| This unit only | Email for specs & price | Email for specs & price |
One request
Request Availability for Your Shortlist.
Email Tommy to discuss these options. The listing IDs will already be in the email subject.
What still needs to be checked?
Confirm frequency, cooling-stage ratings, impedance and its base, taps, vector group, grounding, BIL, site conditions and included scope against the project specification. A table cannot approve the fit.
Match the nameplate to the specification · Review surplus equipment records · Procurement checklist