Your equipment shortlist
Compare equipment before you request it.
Review the published facts side by side. Matching a voltage or MVA rating does not establish compatibility. Ask your project engineer to review the complete unit records.
| Compare | 120 MVA 138/34.5 kV Georgia Solar GSUJJ-TX-004 | 208 MVA 138/34.5 kV Stored Surplus TransformerJJ-TX-201 |
|---|---|---|
| Manufacturer | Georgia Transformer | Manufacturer disclosed in the qualified technical package |
| Rating / output | 72/96/120 MVA; 25.2/33.6/42 MVA tertiary | 125/166/208 MVA |
| Voltage / winding arrangement | 138/34.5 kV with 12 kV buried-delta tertiary | 138 kV HV / 34.5 kV LV |
| Vector group | YNyn0+d1 | Grounded wye / grounded wye |
| Frequency | 60 Hz | 60 Hz |
| Cooling | ONAN / ONAF1 / ONAF2 | ONAN / ONAF1 / ONAF2 |
| Impedance and base | Measured H–X: 6.93% at 72 MVA; design value 7.2% | H–X 9% at 125 MVA (supplied design sheet) |
| Tap changer | HV OLTC; 117.3–158.7 kV (±15%); confirm the final switch and step schedule | HV OLTC ±8 × 1.25% (±10%); no taps shown on X or Y windings |
| Insulation / BIL | HV line 650 kV; HV neutral, LV line and LV neutral 200 kV | HV line 650 kV; HV neutral, LV line and LV neutral 200 kV |
| Quantity represented | 1 documented unit | 1 offered position |
| Technical details / open items | Solar GSU design; ONAN/ONAF1/ONAF2, 60 Hz, three-phase; Vector group YNyn0+d1 with HV OLTC and conservator oil system; Nameplate rating is used; an outline-drawing discrepancy requires final seller confirmation | Supplied design data sheet; final unit-specific nameplate and FAT pending.; Ask J&J for the included U.S.-port shipping, commissioning and manufacturer warranty scope in the written offer.; Technical suitability subject to buyer review; Any warranty provider, scope, transfer eligibility, start date and commissioning boundary must appear in the written quotation.; Design basis: ONAN/ONAF1/ONAF2, 60 Hz, 65 C temperature rise; grounded-wye high and low sides.; HV OLTC design range ±10%; preliminary 13.8 kV open-delta tertiary. Final unit-specific configuration requires approval.; Design H-X impedance: 9% at a 125 MVA base. This is a design-sheet value, not a final tested result. |
| Evidence reviewed | Serial-specific nameplate and approval drawings reviewed | Supplied design data sheet; final unit-specific nameplate and FAT pending |
| Technical value basis | Supplied unit nameplate; the nameplate takes precedence over the differing outline-drawing rating. | Supplied guaranteed design sheet; these are design values, not final tested values for an individually matched unit. |
| Details to confirm | Resolve the outline-drawing rating discrepancy and confirm the final drawing revision; Current preservation, complete tests, dimensions and included accessory schedule | Final unit-specific nameplate, approved revision, tested impedance/losses and final tertiary arrangement; Conductor, OLTC switch specification, complete accessories, current photos and preservation or manufacturing progress |
| Represented condition | Brand new, never used and never energized; approval drawings reviewed | Surplus in storage; service history requires confirmation |
| Equipment location | USA | Dispatch location confirmed with quotation |
| Technical records reviewed | 2026-10-08 | 2026-10-08 |
| Availability | Available; engineering package reviewed; subject to prior sale and written reconfirmation | Stored surplus offered for allocation; current release terms require written confirmation |
| Availability last confirmed | 2026-09-24 | Request current confirmation |
| Shipping estimate | Request a written dispatch and delivery schedule | Release, loading and shipping dates confirmed with quotation |
| Nameplate reviewed | Yes — request the unit package | Not recorded as reviewed; request it |
| Drawings reviewed | Yes — request matching unit drawings | Not recorded as reviewed; request them |
| Factory test report reviewed | Not recorded as reviewed; request test records | Not recorded as reviewed; request test records |
| This unit only | Email for specs & price | Email for specs & price |
One request
Request Availability for Your Shortlist.
Email Tommy to discuss these options. The listing IDs will already be in the email subject.
What still needs to be checked?
Confirm frequency, cooling-stage ratings, impedance and its base, taps, vector group, grounding, BIL, site conditions and included scope against the project specification. A table cannot approve the fit.
Match the nameplate to the specification · Review surplus equipment records · Procurement checklist