| Compare | WEG 120 MVA 230/34.5 kV Transformer OfferJJ-WEG-230-120 | New 220 MVA 230/34.5 kV ABB/Hitachi TransformerJJ-230-220-1 |
|---|---|---|
| Manufacturer | WEG | ABB / Hitachi |
| Rating / output | 72/96/120 MVA | 132/176/220 MVA |
| Voltage / winding arrangement | 230/34.5 kV | 230/34.5 kV with 13.8 kV buried-delta tertiary |
| Vector group | Winding connections to confirm | YNyn0d1 — Wye–Wye / Delta |
| Frequency | Not documented; confirm with J&J | 60 Hz |
| Cooling | Not documented; confirm with J&J | ONAN / ONAF / ODAF |
| Impedance and base | Not documented; confirm with J&J | H–X: 10.47% at 132 MVA, 230/34.5 kV |
| Tap changer | Not documented; confirm with J&J | HV OLTC; nameplate tap table spans 205.8–254.2 kV; confirm the selected tap and final switch schedule |
| Insulation / BIL | Not documented; confirm with J&J | HV line 900 kV; HV neutral, LV and tertiary 200 kV |
| Quantity represented | 1 represented option | 1 unit |
| Technical details / open items | The received September 30 forward repeats an August offer for a WEG 72/96/120 MVA, 230/34.5 kV unit represented as stored in the United States.; Individual new/unused or previously operated condition is not established. This record is excluded from both the new/unused and used/pre-owned filters until condition is confirmed.; The earlier approximate four-week lead time is not a current delivery commitment. Request present allocation and release milestones.; Obtain the individual nameplate, winding connections, frequency, cooling, preservation/service history, test reports and written warranty terms.; This is separate from J&J's WEG 120/24.9 kV 166.667 MVA record and the WEG 230/34.5 kV 88 MVA record. | 132/176/220 MVA, 230 kV grounded-wye high side and 34.5 kV grounded-wye low side; YNyn0d1 connection documented in the manufacturer factory test report; 13.8 kV buried-delta tertiary; 2021 ABB rating-plate drawing; three-phase, 60 Hz, ONAN/ONAF/ODAF cooling; Contact Tommy Marco directly for the technical package, price, and delivery arrangements; Nameplate impedance: 10.47% on a 132 MVA, 230/34.5 kV base; final configuration confirmed with the technical package |
| Evidence reviewed | Received written equipment offer | Manufacturer nameplate and factory test report reviewed |
| Technical value basis | Received written equipment offer; this unit has not been matched to an individual technical package. | Supplied unit nameplate and historical factory photograph; current inspection and matching factory records remain necessary. |
| Details to confirm | Individual condition/service history, nameplate, frequency, cooling/rise and connections; Impedance/base, BIL, taps, conductor/fluid, tests, dimensions/weights and present preservation | Current preservation, complete factory-test reports and included accessory schedule; Overall/shipping dimensions, shipping weight, oil quantity and loading arrangements |
| Represented condition | Individual condition and service history require confirmation | Brand new, never used and never energized |
| Equipment location | USA | USA |
| Technical records reviewed | 2026-10-08 | 2026-10-08 |
| Availability | August offer re-forwarded September 30, 2026; present availability and release timing unconfirmed | Available; confirmed by J&J on September 24, 2026; subject to prior sale and written confirmation |
| Availability last confirmed | Request current confirmation | 2026-09-24 |
| Shipping estimate | Request a written dispatch and delivery schedule | Request a written dispatch and delivery schedule |
| Nameplate reviewed | Not recorded as reviewed; request it | Yes — request the unit package |
| Drawings reviewed | Not recorded as reviewed; request them | Yes — request matching unit drawings |
| Factory test report reviewed | Not recorded as reviewed; request test records | Report reviewed; confirm matching records for each unit |
| This unit only | Email for specs & price | Email for specs & price |
One request
Request Availability for Your Shortlist.
Email Tommy to discuss these options. The listing IDs will already be in the email subject.
What still needs to be checked?
Confirm frequency, cooling-stage ratings, impedance and its base, taps, vector group, grounding, BIL, site conditions and included scope against the project specification. A table cannot approve the fit.
Match the nameplate to the specification · Review surplus equipment records · Procurement checklist