Your equipment shortlist
Compare equipment before you request it.
Review the published facts side by side. Matching a voltage or MVA rating does not establish compatibility. Ask your project engineer to review the complete unit records.
| Compare | ILJIN 167 MVA 230/34.5 kV New / Unused TransformerJJ-ILJIN-230-167 | New 220 MVA 230/34.5 kV ABB/Hitachi TransformerJJ-230-220-1 |
|---|---|---|
| Manufacturer | ILJIN Electric | ABB / Hitachi |
| Rating / output | 100/133/167 MVA | 132/176/220 MVA |
| Voltage / winding arrangement | 230/34.5 kV; tertiary voltage to confirm | 230/34.5 kV with 13.8 kV buried-delta tertiary |
| Vector group | YNyn0+d represented; tertiary clock to confirm | YNyn0d1 — Wye–Wye / Delta |
| Frequency | Not documented; confirm with J&J | 60 Hz |
| Cooling | Not documented; confirm with J&J | ONAN / ONAF / ODAF |
| Impedance and base | Not documented; confirm with J&J | H–X: 10.47% at 132 MVA, 230/34.5 kV |
| Tap changer | Not documented; confirm with J&J | HV OLTC; nameplate tap table spans 205.8–254.2 kV; confirm the selected tap and final switch schedule |
| Insulation / BIL | Not documented; confirm with J&J | HV line 900 kV; HV neutral, LV and tertiary 200 kV |
| Quantity represented | 1 represented unit | 1 unit |
| Technical details / open items | The individual August offer expressly identifies this ILJIN option as new/unused and never energized; that offer was forwarded again September 30, 2026.; A separate September 30 equipment table repeats 100/133/167 MVA and 230/34.5 kV. Dispatch location and allocation require current confirmation through J&J.; The supplied vector description is YNyn0+d. Obtain the individual nameplate, tertiary rating and voltage, vector clock, frequency, cooling stages and test records before duty approval.; Confirm preservation and storage history, actual warranty provider and transferable written coverage, loading and shipping terms with the quotation.; This ILJIN offer is distinct from the separately listed Fortune Electric 167 MVA transformer; no additional Fortune unit is implied. | 132/176/220 MVA, 230 kV grounded-wye high side and 34.5 kV grounded-wye low side; YNyn0d1 connection documented in the manufacturer factory test report; 13.8 kV buried-delta tertiary; 2021 ABB rating-plate drawing; three-phase, 60 Hz, ONAN/ONAF/ODAF cooling; Contact Tommy Marco directly for the technical package, price, and delivery arrangements; Nameplate impedance: 10.47% on a 132 MVA, 230/34.5 kV base; final configuration confirmed with the technical package |
| Evidence reviewed | Individual written offer, repeated in a September 30 equipment listing | Manufacturer nameplate and factory test report reviewed |
| Technical value basis | Received written equipment offer; individual technical records require review. | Supplied unit nameplate and historical factory photograph; current inspection and matching factory records remain necessary. |
| Details to confirm | Individual nameplate, frequency, cooling/rise, tertiary duty and vector clock; Impedance/base, BIL, taps, copper/fluid specification, factory tests, preservation and transport scope | Current preservation, complete factory-test reports and included accessory schedule; Overall/shipping dimensions, shipping weight, oil quantity and loading arrangements |
| Represented condition | New / unused and never energized, as explicitly represented in the offer | Brand new, never used and never energized |
| Equipment location | International; dispatch location confirmed with quotation | USA |
| Technical records reviewed | 2026-10-08 | 2026-10-08 |
| Availability | Listed in received September 30, 2026 offers; current allocation, condition and dispatch timing require written confirmation | Available; confirmed by J&J on September 24, 2026; subject to prior sale and written confirmation |
| Availability last confirmed | Request current confirmation | 2026-09-24 |
| Shipping estimate | Request a written dispatch and delivery schedule | Request a written dispatch and delivery schedule |
| Nameplate reviewed | Not recorded as reviewed; request it | Yes — request the unit package |
| Drawings reviewed | Not recorded as reviewed; request them | Yes — request matching unit drawings |
| Factory test report reviewed | Not recorded as reviewed; request test records | Report reviewed; confirm matching records for each unit |
| This unit only | Email for specs & price | Email for specs & price |
One request
Request Availability for Your Shortlist.
Email Tommy to discuss these options. The listing IDs will already be in the email subject.
What still needs to be checked?
Confirm frequency, cooling-stage ratings, impedance and its base, taps, vector group, grounding, BIL, site conditions and included scope against the project specification. A table cannot approve the fit.
Match the nameplate to the specification · Review surplus equipment records · Procurement checklist