Sugar Land, Texas · Nationwide power-equipment sales

346-276-9540 tommy@jjtransformers.com

Your equipment shortlist

Compare equipment before you request it.

Review the published facts side by side. Matching a voltage or MVA rating does not establish compatibility. Ask your project engineer to review the complete unit records.

Published specifications for 2 alternatives. Availability remains subject to prior sale and written reconfirmation.
Compare166.667 MVA 120/24.9 kV WEG TransformerJJ-WEG-120-167120 MVA 138/34.5 kV Georgia Solar GSUJJ-GA424A
ManufacturerWEGGeorgia Transformer
Rating / output100/133.333/166.667 MVA72/96/120 MVA; 25.2/33.6/42 MVA tertiary
Voltage / winding arrangement120 kV delta / 24.9 kV grounded wye138/34.5 kV with 12 kV buried-delta tertiary
Quantity represented1 nameplate-documented unit1 documented unit - GA424A
Technical details / open itemsThree-phase, 60 Hz power regulating transformer; manufactured by WEG Transformadores Mexico in July 2015; Continuous nameplate ratings: 100,000 / 133,333 / 166,667 kVA with KNAN / KNAF / KNAF cooling; Vector group Dyn1; 120 kV delta high side and 24,900Y/14,376 V low side; High-side OLTC with 16 raise and 16 lower steps of 0.625%; Nameplate photograph and serial details are shared privately; condition, test records, included scope and delivery schedule require confirmationSolar GSU design; ONAN/ONAF1/ONAF2, 60 Hz, three-phase; Vector group YNyn0+d1 with HV OLTC and conservator oil system; Nameplate rating is used; an outline-drawing discrepancy requires final seller confirmation
Evidence reviewedUnit nameplate photograph reviewedSerial-specific nameplate and approval drawings reviewed
Represented conditionCurrent condition and operating history to confirm with J&J; July 2015 manufacture shown on nameplateRepresented as unused and never energized; current condition requires written reconfirmation; approval drawings reviewed
Technical records reviewed2026-09-212026-09-03
AvailabilityAvailable for inquiry; subject to prior sale and written confirmationRepresented available; engineering package reviewed; subject to prior sale and written reconfirmation
This unit onlyEmail for specs & price Email for specs & price

One request

Request Availability for Your Shortlist.

Email Tommy to discuss these options. The listing IDs will already be in the email subject.

Email this shortlist

What still needs to be checked?

Confirm frequency, cooling-stage ratings, impedance and its base, taps, vector group, grounding, BIL, site conditions and included scope against the project specification. A table cannot approve the fit.

Match the nameplate to the specification · Review surplus equipment records · Procurement checklist

Call Email Sales